Group 11 Rotary Damper Drives and Actuators
Control Options
What is a Control Option?
Group 11 Beck drives have a model number such as 11-150, 11-160, 11-200, 11-260, 11-300, 11-360, 11-400, 11-460, or 11-430. Each of these drives has the capability to be
equipped with different electronics combinations, which are called control
options. The control option number will replace the last zero in the model
number when specifying a drive model and control option. For example, a
model 11-400 drive that is setup to use the control option 9 electronics
would be considered a model 11-409 drive. A basic description for each
control option is provided below. For details on the electronics components,
please visit the Group 11 Electronics section.
Please click on a control option for a description or reference the control option summary chart below.
9 | 8 | 7 | 6 | 5 | 4 | 3
Control Option Summary Chart *
Control Option |
Control
Mode |
Installed
Control
Board |
Standard
Control
Input |
Installed
Position
Sensor |
Standard
Position Feedback |
|
Modulating |
DCM-2 |
4-20 mA |
CPS-2 |
420 mA |
|
Modulating |
ESR-4 |
4-20 mA |
CPS-2 |
420 mA
|
|
Modulating |
ESR-4 |
4-20 mA |
Film Pot. |
None |
|
Modulating |
None |
120 V ac |
CPS-2 |
420 mA
|
|
Modulating |
None |
120 V ac |
Film Pot. |
Film Pot. |
|
5-position |
None |
120 V ac |
None |
None |
|
3-position |
None |
120 V ac |
None |
None |
|
2-position (open/close) |
None |
120 V ac |
None |
None |
*Please contact the factory to discuss desired options not shown here.
CONTROL OPTION 9 - The standard modulating drive offering is the
control option 9. Control option 9 units are equipped with the Beck DCM (Digital Control Module) and CPS (Contactless Position Sensor). The option
9 drives may be controlled with a 4-20 mA or 1-5Vdc signal and have an
integral 4-20 mA position feedback signal. The microprocessor based DCM provides a multitude of flexibility for setup, calibration, and diagnostics
including HART communications, on-board pushbuttons for calibrating
stroke, on-board diagnostic status, stall protection circuitry, and status
alerts. Typical Arrangement
CONTROL OPTION 8 - The control option 8 drive is also a modulating unit,
but is equipped with an ESR (Electronic Signal Receiver) and CPS (Contactless Position Sensor). The time-proven analog ESR control board
provides the same excellent control that a control option 9 drive offers, but
lacks many added setup, operating, and diagnostic features afforded by the
DCM. While the standard control option 8 units may be controlled by a 4-20
mA signal with an integral 4-20 mA position feedback, less common
signaling options are availble upon request. Typical Arrangement
CONTROL OPTION 7 - The control option 7 drive is a modulating unit that
is offered without an external position feedback signal. The option 7 drive is
equipped with the ESR (Electronic Signal Receiver) for control and a 1000-
ohm film potentiometer to derive an internal position reading. While the
standard control option 7 units may be controlled by a 4-20 mA signal, less
common signaling options are availble upon request. An optional auxiliary
pot for external position feedback is also available upon request. Typical Arrangement
CONTROL OPTION 6 - The control option 6 drive is a modulating unit
controlled with 120 VAC direct to the motor. A CPS (Contactless Position
Sensor) provides a 4-20 mA position feedback signal; less common
signaling options are availble upon request. Typical Arrangement
CONTROL OPTION 5 - The control option 5 drive is a modulating unit
controlled with 120 VAC direct to the motor. A 1000-ohm film potentiometer
is standard to derive an external position reading. An optional auxiliary pot
for external position feedback is also available upon request. Typical Arrangement
CONTROL OPTION 4 - The control option 4 drive is a Multi-position unit
controlled with 120 VAC direct to the motor through a series of camoperated
limit switches. The drive may be factory configured for three to six
distinct positions anywhere in travel including two end-of-travel positions. Typical Arrangement
CONTROL OPTION 3 - The control option 3 drive is an open/close unit
controlled with 120 VAC direct to the motor. When the drive hits the limit
switch at either of the two end-of-travel positions, power is cut to the
motor. Typical Arrangement
|