Beck: Electric Actuators for Industrial Process Control
Beck: Electric Actuators for Industrial Process Control How to Order Site Map Contact Us
Home
The Beck Advantage
Electric Actuator Products
Services & Support
Actuator Applications
Industries
Technical Library & Links
News & Events

Group 11
Rotary Damper Drives and Actuators

Product Features & Specifications

Data Sheets, Drawings, & Manuals

Control Options

Product Selector:

Group 11 Rotary Damper Drives and Actuators

General Specifications

Input Power
120 V ac, single-phase
240 V ac, single-phase

Operating Conditions
-40° to 85° C. (-40° to 185° F.), 0% to 99% relative humidity

Isolation
Demand Input and Position Feedback signals are isolated from the ground and the ac power line.

Action on Loss of Power
Stays in place.

Action on Loss of Input Signal (Power On)
Stays in place or, on some drives, is field configurable to move to any preset position.

Limit Switches
Two SPDT switches (one for each direction of travel) provide over-travel protection.

Auxiliary Switches
Up to four 6 A, 120 V ac switches available. Switches are labeled S1 to S4 and are cam-operated and field-adjustable.

Handswitch
Permits local electrical operation, independent of controller signal. Standard on all units. An optional auxiliary contact can be used to indicate that the Handswitch is in "AUTO" mode or to sound an alarm if it is taken out of "AUTO".

Modulating Control

 

Digital Control Module (DCM)

Electronic Signal Receiver (ESR) Direct AC
Input Signal Options
N/A
Adjustability for Split Range Operation
4 to 1
2 to 1
N/A
Deadband
0.6% of span (configurable)
0.6% of span
N/A
Minimum Step
0.1% typical
0.15% typical
0.1° function of control system capabilities
Feedback Options
Stall Protection (Protects drive and driven elements under stall conditions)
Standard. Integral to electronics. Time to stall is configurable from 300 seconds down to 30 seconds.
Optional. Requires a Stall Protection Module (SPM) to shut off power to the motor.
Note: (1) Models approved for use in Hazardous classified locations are available—contact a Beck Sales or Application Engineer for details.