General Specifications

Download a PDF copy of the Group 22 General Specifications

Output Torque and Timing

Model #
Torque in lb-ft (N•m)
Stroke Time
(sec./100°)
configurable
22-309
3,000 (4,067)
30-300
22-409
4,000 (5,423)
15-300
22-809
8,000 (10,846)
15-300

Drive Current Rating in Amps (listed by operating voltage)*

 
Model #
Operating Voltage (Volts AC)
1 - phase
3 - phase
120
240
208
240
380
416
480
575
22-309
6.0
3.0
3.5
3.0
1.9
1.7
1.5
1.3
22-409
N/A
N/A
4.0
3.5
2.2
2.0
1.7
1.4
22-809
N/A
N/A
6.9
6.0
3.8
3.5
3.0
2.5

* Operating voltage tolerance is +10% to -15% and all drive models listed may be operated with a 60 Hz or 50 Hz frequency.

The gray shaded areas indicate the current rating for the standard operating voltage configuration. Non-standard operating voltages for model 22-309 and 22-409 are available with an optional transformer.

Weight

Model #
Approximate Weight in lbs (kgs)**
22-309
515 (234)
22-409
515 (234)
22-809
1,100 (567)

** Standard configuration weights shown, the actual weight may vary depending on the selected options.

Additional Specifications

Operating Conditions
–40° to 85° C. (–40° to 185° F.)
0 to 99% relative humidity
Demand Input Signal Range
4–20 mA, 1–5 V dc
Minimum Step
0.1° typical
Linearity
±1% of span, max. independent error
Hysteresis
0.25% of span at any point
Demand Input Signal
Characterization
Linear: Drive output shaft moves proportionally to the input signal.
Square: Drive output shaft moves proportionally to the square of the input signal.
Position Feedback
Signal
Demand input and position Feedback signals are isolated from ground and the ac power line. Signal buffering provides 24 Vdc isolation between the Demand and Feedback signals.
Overtorque Protection
If the output torque of the drive exceeds 115% of the drive rating, the motor will shut off (feature can be enabled/disabled).
Action on Loss of
Input Signal (Power
On)
Stays in place or runs to any preset position (configurable).
Stall Protection
If the motor tries to run in one direction for more than 300 seconds (configurable from 30 to 300 seconds), the motor will shut off.
Over-travel Protection
Switches
Two SPDT, one for CW and one for CCW limit of output shaft travel. Standard switch setting allows for 100° of travel.
Non-dedicated
Switches (Field
Adjustable)
Two SPDT, rated for 1 A, 250 Vac
Handswitch
Permits local electrical operation, independent of Demand input signal.
Handwheel (and
Handcrank on the
model 22-809)
Provides manual operation without electrical power.
Enclosure
Precision-machined aluminum alloy castings, painted with corrosion-resistant polyurethane paint, provide a rugged, dust-tight, weatherproof enclosure.
Mounting Orientation
Upright, as depicted in
outline dimension drawings
Customer Wiring
Terminals accommodate up to
12 AWG (3.31 mm2)
Motor
Does not coast or overshoot and will not overheat, even under continuous modulation
Gear Train
High efficiency, precision-cut, heat-treated alloy steel and ductile iron spur gears enclosed in and permanently lubricated by a grease-filled housing are designed for long life and minimal wear.
Mechanical Stops
Prevent over-travel during automatic ormanual operation
Standards***

UL Listed
CE Compliant

*** NOTE: May not be available with all options and models. For more infomration or to inquire about standards not specifically listed, please call Beck for more information at 215-968-4600.