General Specifications

Download a PDF copy of the Group 29 General Specifications

Output Thrust and Timing (all 29-100 models)

Thrust (lbs.)
Stroke Timing (seconds/inch)
1000
10

Drive Power Options (all 29-100 models)

120 Vac, single-phase, 50 or 60 Hz
240 Vac, single-phase, 50 or 60 Hz

Additional Specifications

Weight
Approximately 80 lbs. including yoke
Operating Conditions
–40° to 85° C. (–40° to 185° F.)
0 to 99% relative humidity
Communications Interface
HART© protocol and local pushbutton/LED panel and RS-232 serial commands
Demand Input Signal
Range
4–20 mA, 1–5 V dc
Minimum Step
0.1° of span
Hysteresis
0.25% of span at any point
Demand Input Signal
Characterization
Linear: Drive output shaft moves proportionally to the input signal.
Square: Drive output shaft moves proportionally to the square of the input signal.
Custom: 20 segment configurable curve fit
Position Feedback
Signal
4-20 mA
Isolation
Demand input and position Feedback signals are isolated from ground and the ac power line. Signal buffering provides 24 V dc isolation between the Demand and Feedback signals.
Action on Loss of
Power
Output shaft stays in last position
Action on Loss of Input Signal (Power on)
Stay in place or runs to any preset position (configurable)
Over-thrust Protection
If the output thrust of the drive exceeds 115% of the drive rating, the motor will shut off (feature can be enabled / disabled).
Stall Protection
If the motor tries to run in one direction for more than 300 seconds (configurable from 30 to 300 seconds), the motor will shut off.
Over-travel Protection Switches
Two Form C (Retract and Extend) provide over-travel protection
Auxiliary Switches
(Field Adjustable)
Two Form C and two Form,
all rated for 1 A, 250 V ac
Customer Wiring
Terminals accommodate up to 12 AWG
(3.31 mm^2)
Handswitch
Permits local electrical operation, independent of Demand input signal.
Handwheel
Provides manual operation without electrical power.
Motor
120 Vac, single-phase, no burnout, noncoasting. Capable of 60 starts per minute
Enclosure
Precision-machined aluminum alloy castings, painted with corrosion-resistant polyurethane paint, to provide a rugged, dust-tight, weatherproof enclosure designed to meet NEMA 4X standards.
Mounting Orientation
Can be mounted in any orientation